Portfolio Retrofit Payback

LED retrofit payback for every building you own

List your buildings and the old fixtures in each one. See the energy cost before and after, the project cost, the rebates that apply, the payback, the crew days and a monthly service plan price, site by site and for the whole portfolio.

Example

Savings and cost by site

Net project costRebateEnergy savings per year

Cumulative cash flow

Cash position, all sitesPayback point

Your buildings

Enter one row for each building. Count the old fixtures by type. The power rate starts at the state average; type your own rate from a recent bill.

BuildingTypeSq ftStateUtility Rate $/kWhHours a dayDays a week 400 W MH high bay6-lamp T8 high bay4 ft T8 (2 lamp)250 W MH area lightWall pack (175 W MH) Remove

Assumptions you can change

Results by site

Energy and cost per year before and after the retrofit. The project cost includes LED fixtures, labor, lifts and disposal.

Crew schedule

Crews do the sites with the fastest payback first. One crew day is one crew working one full day.

Rebate check

We read each utility program page and the IRS page on November 7, 2026. Rebates change often. Get pre-approval in writing before you order fixtures.

Programs we checked

Questions and answers

Short answers for owners and managers of many buildings. Each rule or number from an outside source links to that source.

How does this page work out the payback?

Payback is the net project cost after rebates, divided by the energy savings in one year. This is a simple payback. It does not discount future savings, and it ignores changes in power prices (NIST Handbook 135). It also ignores costs and savings after the payback date. NIST calls payback a rough guide for accept or reject decisions, and a screening tool. Ask for a life-cycle cost study for a large program. On this page, Fast is a payback of 3 years or less, and Slow is more than 6 years. Fair is in between. These bands are our own.

What does FPL pay for LED lighting in a business?

FPL pays a rebate for each qualifying fixture in its Business Lighting Program. The rebate is $10 for an LED linear fixture and $20 for an LED fixture of 0 to 140 W. It is $40 for an LED fixture over 140 W (FPL program standards, effective September 1, 2025). The fixtures must be new, ceiling mounted, fully integrated and hardwired, and they must replace less efficient interior lighting. They must be on the DLC or ENERGY STAR list. They must run from 3 to 6 p.m. on weekdays, June 1 through September 30. A fixture that the code requires does not qualify. The program is for interior lighting in existing buildings (FPL program page).

Do I need the utility's approval before work starts?

It depends on the utility. FPL asks you to contact its program specialist to confirm that the project qualifies, before the install or after it (FPL program page). Tampa Electric requires pre-approval (Tampa Electric lighting rebate page). OUC asks for its project approval and funding commitment before the work begins (OUC program page). Rebates change often. Get pre-approval in writing before you order fixtures, where the utility offers it.

Do we need lighting controls in a retrofit?

The energy code can require them. In Florida, new lighting in an alteration must meet the lighting and commissioning sections of the energy code (Florida Building Code, Energy Conservation, 8th Edition (2023), Section C503.5). The exception is a job that replaces less than 10 percent of the fixtures in a space, without more lighting power. The lighting section calls for occupant sensors in spaces such as warehouse storage areas, restrooms and enclosed offices (Section C405.2). Most other areas need time-switch controls. The controls must pass functional tests before the final inspection (Section C408.3). DOE also says to consider occupancy sensors and daylight dimming for more savings (DOE FEMP). This page does not price controls or count their savings. Ask your designer and the building department which controls your job needs.

Does an LED retrofit lower maintenance costs?

For fluorescent fixtures, DOE says yes. Fluorescent fixtures need regular lamp and ballast changes. LED parts have very long lives that in general do not need replacement (DOE FEMP). DOE says that this greatly reduces maintenance needs and costs. It says to consider these savings when you replace fluorescent fixtures. This page does not count them, so its payback leaves them out. Add your past lamp and ballast costs to the notes for your brief.

Should we retrofit every building at once, or in phases?

You can do either. The crew schedule on this page starts with the buildings that pay back fastest. Check the rebate caps before you spread the work over several years. For example, OUC caps its rebate at $200,000 per customer per year, October to September (OUC program page). This page applies the caps that a program sets for one project or one building. It does not apply a yearly cap per customer. Put your budget for each year in the notes for your brief.

What does the monthly service plan cover?

The plan price on this page is our assumption, not a quote. The plan covers a night check of exterior lights, photocell and time clock checks, and warranty claims. It also covers labor to swap failed drivers or fixtures under warranty. The price formula is in the note under "Assumptions you can change". DOE notes that troffers, linear and industrial fixtures that meet the DLC standard requirements have five-year maker warranties (DOE FEMP). LED light output also drops with age. DOE says to start planning replacement when the output falls 25 percent below the level when new.

Can we still claim the 179D tax deduction?

Not for new work. The IRS says the deduction ends for property whose construction begins after June 30, 2026 (IRS 179D page). The deduction covered interior lighting, heating, cooling, ventilation and hot water, or the building envelope. The property had to be certified to meet energy savings rules. One rule was a plan to cut annual energy and power costs by 25 percent or more. Ask a tax advisor about work that began on or before June 30, 2026. This page does not give tax advice.

Send to a lighting pro

Copy this brief and send it to the lighting designer or contractor of your choice. Nothing leaves this page until you paste it.


        

What happens next

  1. A pro checks your fixture counts on a walk of each site.
  2. The pro picks DLC-listed fixtures and applies for each rebate before work starts.
  3. You get one price for the whole portfolio and a crew schedule.

A Lighting Certified (LC) designer reviews South Florida projects (Palm Beach, Broward and Miami-Dade). A partner reviews projects in other areas.

How it works

1. Energy

Each old fixture uses the input watts from a utility standard wattage table. Each LED uses the watts on its spec sheet. Interior lights run your hours; exterior lights run 3,600 hours a year.

2. Cost

Fixture prices are public prices we found online. Labor uses hours per fixture and your labor rate. Lifts, disposal and parts are a cost per fixture.

3. Rebates

We apply the published rate of each program and its cap. A program without a published rate counts as zero until the utility confirms a rate. FPL pays only for fixtures on the DLC or ENERGY STAR list, so we count its rebate only when the LED we priced shows a listing.

4. Payback

Payback is the net cost after rebates divided by the energy savings per year. We do not count lower maintenance or a change in power rates.

Notes for the owner

Built 2026-11-07. Data checked November 7, 2026. One self-contained page; all data is inside it.

Our assumptions

  • Labor rate: $85 an hour. Our assumption: a billed rate for a licensed electrician, with payroll costs, insurance, truck, overhead and profit. The BLS mean wage for electricians was $27.72 an hour in Florida and $34.37 in the US (May 2025).
  • Labor hours per fixture: 400 W MH high bay 1.5 h, 6-lamp T8 high bay 1.5 h, 4 ft T8, 2 lamp 1.0 h, 250 W MH area light 2.0 h, 175 W MH wall pack 1.25 h, plus 4 h per site for setup and cleanup. Basis: CPUC 2010-2012 WO017 Ex Ante Measure Cost Study (Itron, May 27, 2014), Table 4-6: HID to T5 high bay fixture, lift accessible, 2.02 labor hours per fixture; fluorescent fixtures 1.15 to 1.26 hours. Report text (p. 4-14) compares the high bay value with artificial bids (0.96 h) and RSMeans (2 h). LED fixtures are lighter than these, so we use 1.5 h for high bays.
  • Lifts, disposal and parts per fixture: 400 W MH high bay $38 (WO017 Table 4-6, HID high bay: misc $5.69 + lift $14.63 + disposal $17.99 = $38.31 per fixture (2014 California). Rounded to $38.); 6-lamp T8 high bay $38 (Same high bay basis as the 400 W metal halide row (lift and disposal).); 4 ft T8, 2 lamp $12 (Our assumption: lamp and ballast disposal, wire nuts and small parts, ladder work. WO017 Table 4-6 shows 1.15 to 1.26 labor hours for fluorescent fixtures.); 250 W MH area light $45 (Our assumption: bucket truck share, pole-top adapter, disposal.); 175 W MH wall pack $20 (Our assumption: lift or ladder share, disposal, sealant and parts.)
  • Crew: 2 electricians, 8 h a day, 1 crew. Crew days round up to the next half day per site. Sites are scheduled fastest payback first.
  • Exterior hours: 3,600 h a year for area lights and wall packs. DOE FEMP uses 3,600 operating hours a year for exterior lighting. The Mid-Atlantic TRM v10 uses 3,604 hours for pole and wall-mounted area lights (metered).
  • Fixture prices: Low, typical and high are the lowest, the middle and the highest public price we found for each LED type (2026-11-07). Distributor quotes to a contractor can differ. The typical price is the median of the listings. No contractor markup is added on fixtures.
  • Service plan price: Our assumption. A monthly plan per site covers a night check of exterior lights, photocell and time clock checks, warranty claims, and labor to swap failed drivers or fixtures under warranty. Price = $40 per site + $0.50 per interior fixture + $1.25 per exterior fixture, each month.
  • TECO rate split: Our assumption for the TECO rate split: warehouse floors are not air-conditioned; flex, office and retail space is air-conditioned. Exterior lights count as non-conditioned space.
  • FPL: We flag an FPL site when it runs fewer than 5 days a week or fewer than 10 hours a day, because FPL pays only for fixtures that run 3 to 6 p.m. on summer weekdays. The LED linear high bay (104 W) counts as a bay fixture at $20, not as LED linear at $10. FPL pays only for fixtures on the DLC or ENERGY STAR list (program standards, Sec. 2.2). We count the FPL rebate for a fixture type only when each product behind the chosen price shows a listing. A product with "not stated" gets no rebate.
  • Georgia Power: the 6-lamp T8 high bay is 6 x 32 W = 192 W nominal, so it takes the $40 tier (220 W fluorescent and less). The 50% cap uses the fixture price only.
  • OUC: the 50% cap uses the indoor part of the project cost.
  • SRP: interior lights use the low rate of $0.25 per watt; the page shows up to $0.35.
  • Power rate: the default for each site is the EIA commercial average for its state, year to date through August 2026 (Florida $0.1178/kWh). The average includes demand charges, so it stands in for the full bill rate.
  • Not counted: lamp and ballast maintenance savings, lower cooling load, rate changes, financing, sales tax, permits and controls (occupancy sensors).

To confirm before launch (LC review)

  • Labor hours per fixture and the 4 h site setup, against real job records.
  • The installed labor rate of $85 an hour for Florida work.
  • Lifts, disposal and parts per fixture (high bay $38 from a 2014 California study; others are our numbers).
  • The LED wattage chosen for each old fixture type, and that each gives enough light for the space (no photometric check here).
  • The service plan price basis ($40 a site + $0.50 per interior fixture + $1.25 per exterior fixture, a month) and what the plan covers.
  • TECO: whether exterior lights take the non-conditioned rate, and our warehouse versus conditioned split.
  • FPL: whether a linear high bay is LED linear ($10) or a bay fixture ($20 or $40).
  • Duke Energy Florida and JEA current lighting rates (we could not open their rate pages).
  • The 179D end date for retrofits that began construction on or before June 30, 2026 (ask a tax advisor).

Engine limits

  • Energy is connected watts times hours. No controls, dimming or partial schedules.
  • One power rate per site for every kWh. No demand charge split and no time-of-use rates.
  • Simple payback and a straight-line cash flow. No discount rate and no rate change over time.
  • Five old fixture types only. Other types (1,000 W metal halide, T12, canopy, flood) need new rows in data/fixtures.json.
  • Rebates use the published rate and the caps on each page. Program-level annual caps per customer (OUC $200,000, JEA $100,000, SRP $300,000) are not summed across sites.
  • Oncor (Texas) was not checked: its 2026 program deck did not load. Texas sites count zero rebate.
  • Duke Energy Florida and JEA count zero until their rates are confirmed.

Routing plan

  • The brief is copy-only. There is no form, no backend and no email address on the page.
  • Routing text on the page: South Florida projects (Palm Beach, Broward and Miami-Dade) go to a Lighting Certified (LC) designer; other areas go to a partner. No partners are signed yet.
  • Working name not checked. Run the name check before any launch. No repo yet; run the repo-setup skill before any deploy.

Sources

  1. FPL Business Lighting Program page (seen 2026-11-07)
  2. FPL Business Lighting Program Standards, effective September 1, 2025 (PDF) (seen 2026-11-07)
  3. Tampa Electric business lighting rebate page (seen 2026-11-07)
  4. OUC Commercial & Industrial Custom Incentive Program page (seen 2026-11-07)
  5. Duke Energy Florida, Demand Side Management Annual Report for 2025, Florida PSC (Smart $aver Business, page 10) (seen 2026-11-07)
  6. Duke Energy Smart $aver business page (HTTP 403 to our reader; not read) (seen 2026-11-07)
  7. JEA Business Rebates Program flyer, updated 4/25/24 (copy on the St. Johns County site) (seen 2026-11-07)
  8. JEA Business Rebate Program page (shows a human check; not read) (seen 2026-11-07)
  9. Georgia Power Commercial 2026-28 Existing Building Lighting rate sheet (PDF) (seen 2026-11-07)
  10. SRP Business Solutions Standard fact sheet, effective FY27 (May 1, 2026 to April 30, 2027) (seen 2026-11-07)
  11. SRP Business Solutions Lighting sheet, FY26 (same rates) (seen 2026-11-07)
  12. Dominion Energy news release, February 24, 2026: small business rebates (South Carolina) (seen 2026-11-07)
  13. IRS: Energy efficient commercial buildings deduction (179D), page last reviewed October 27, 2026 (seen 2026-11-07)
  14. Lighting Tables for Existing/Base Equipment (Austin Utilities, Owatonna Public Utilities, Rochester Public Utilities), dated 2/1/26 (seen 2026-11-07)
  15. CPUC 2010-2012 WO017 Ex Ante Measure Cost Study, Final Report (Itron, 2014), Tables 4-6 and 4-10 (seen 2026-11-07)
  16. EIA Electric Power Monthly, Table 5.6.B (commercial, August 2026 year to date) (seen 2026-11-07)
  17. BLS OEWS May 2025, electricians (47-2111), mean hourly wage: Florida series OEUS120000000000047211103 ($27.72), US series OEUN000000000000047211103 ($34.37) (seen 2026-11-07)
  18. DOE FEMP, Purchasing energy-efficient exterior lighting (3,600 operating hours a year) (seen 2026-11-07)
  19. Mid-Atlantic Technical Reference Manual v10 (NEEP, May 2020), outdoor area lighting hours 3,604 (seen 2026-11-07)

LED product prices (public pages)

Ask a lighting designer about this project

Send your plan to Holzer Lighting in Boca Raton, Florida. Holzer Lighting designs, specifies and buys lighting for owners, managers, designers and builders.

A designer reads your brief and contacts you. The designer checks the rules, the light levels and the prices for your site. This page gives planning estimates only.

You can also email info@holzerlighting.com or call 561.508.8990.

About Holzer Lighting

Other free lighting tools:

Holzer Lighting gets your details and the project brief from this page. They use them only to answer you.