Emergency Lighting Check
Florida fire code, NFPA 101 Section 7.9.3

Will your emergency lights stay on when the power fails?

Enter your building. See the tests that the Florida fire code requires, get a 12-month test log to print, estimate your units, and plan the repairs with a planning cost range.

ExampleA 20-story condo in Miami-Dade with 2 stairwells and 2 garage levels. The last 90-minute test was 13 months ago. Change any value to check your own building.

Your building
County
A new type loads example sizes. Change them to match your building.
Your units
Number of units
A unit is one emergency light or one exit sign.
Estimate setting: spacing
Power and batteries
Look at the label inside one unit, or ask your electrician.
Tests
The first of this weekday in each month keeps 4 or 5 weeks between tests.

Your result

Your next 12 tests

    The rules we found

    We read each rule in an official or primary source. Each card gives the rule in plain words, the section number and the source. The fire official has the final word for your building.

    The code edition in Florida

    Rule 69A-60.004, F.A.C.

    Edition in force today

    Florida enforces NFPA 101, the Life Safety Code, Florida 2021 Edition. It is part of the Florida Fire Prevention Code, 8th Edition. The 8th Edition took effect on December 31, 2023.

    Sources: Rule 69A-60.004, F.A.C.; State Fire Marshal FFPC page

    The tests

    NFPA 101, 7.9.3.1.1

    Monthly test

    Do a functional test of each emergency light every month. Each test runs for at least 30 seconds. Keep at least 3 weeks and not more than 5 weeks between tests. The fire official can approve a longer interval.

    Sources: Iowa test log; Minnesota guide

    NFPA 101, 7.9.3.1.1

    90-minute test

    Once a year, do a functional test of battery-powered emergency lighting for at least 90 minutes (1.5 hours).

    Sources: Iowa test log; Minnesota guide

    NFPA 101, 7.9.3.1.1

    Fully on for the whole test

    The equipment must stay fully on for the whole monthly test and the whole 90-minute test. A unit that goes dark early fails.

    Source: Minnesota guide

    NFPA 101, 7.9.3.1.1(5)

    Written records

    The owner keeps written records of the visual checks and the tests. The fire official can ask to see them.

    Sources: Iowa test log; Minnesota guide

    NFPA 101, 7.9.3.1.2

    Self-testing units

    A self-testing unit runs a 30-second test and a check at least every 30 days. It shows a failure on a status light. Look at each unit every month. Do the 90-minute test once a year.

    Source: Minnesota guide

    NFPA 101, 7.9.3.1.3

    Computer-based systems

    A computer-based self-testing system runs the monthly test and the 90-minute test by itself. It must keep a history of tests and failures.

    Source: Minnesota guide

    NFPA 101, 7.10.9.2

    Exit signs with a battery

    An exit sign with a battery for emergency light gets the same tests as an emergency light.

    Source: Minnesota guide

    The state documents that we read quote or cite the 2012 edition of NFPA 101. Florida enforces the 2021 edition. The NFPA free reader shows the 2021 text after you sign in to a free account. Sources: Iowa test log; Minnesota guide; NFPA free access.

    How long and how bright

    FBC 1008.3.5

    Light level on the exit path

    At the start, the exit path gets an average of 1 footcandle and at least 0.1 footcandle at any point, at the floor. After 90 minutes, the level can drop to 0.6 and 0.06 footcandle. The highest level must not be more than 40 times the lowest.

    Source: Florida Building Code, Chapter 10

    FBC 1008.3.1 to 1008.3.3

    Where the emergency light goes

    Where a building or space needs two or more exits, the emergency system lights the exit path. This includes aisles, corridors, exit stairways and ramps, and exit passageways. It also includes exit discharge areas and outside landings at exit doors. The system also lights electrical rooms, fire command centers, fire pump rooms, generator rooms and public restrooms over 300 sq ft.

    Source: Florida Building Code, Chapter 10

    FBC 1013.5 and 1013.6.3

    Exit sign light

    Exit signs stay lit at all times. An internally lit exit sign must be listed and labeled to UL 924. An externally lit exit sign needs power for at least 90 minutes after a power failure.

    Source: Florida Building Code, Chapter 10

    Local rules

    These are the county rules that we read. Your county is marked when you use the check. Cities can have their own amendments.

    Palm Beach County

    Palm Beach County local amendments to the FFPC, Table 1.3.8.1

    Fire inspection schedule

    The schedule lists a yearly fire inspection for apartment buildings, hotels and dormitories, storage and industrial buildings. Business and mercantile spaces get an inspection every year or every 3 years, by type.

    Source: Palm Beach County amendments

    Palm Beach County local amendments to the FFPC, 1.3.1.1

    Where these amendments apply

    They apply where Palm Beach County Fire Rescue serves. This includes the unincorporated area and the cities that use its fire service. Other cities can have their own amendments.

    Sources: Palm Beach County amendments; State Fire Marshal local amendments

    Broward County

    BORA Policy 05-05

    Building safety inspection

    Buildings get a building safety inspection at 25 years, then every 10 years. Buildings under 3,500 sq ft are exempt. The electrical part says exit sign lights and emergency lighting must be in good working condition.

    Source: BORA Policy 05-05

    BORA Policy 05-05

    Who signs the report

    A Florida licensed engineer or architect seals the inspection report. A licensed professional who works in electrical design completes the electrical form.

    Source: BORA Policy 05-05

    Broward local amendments to the FFPC, F-103.3.1.7

    Fire inspections

    The fire department inspects buildings as often as needed, and at least once a year. This includes the common areas.

    Source: Broward amendments

    Miami-Dade County

    Code of Miami-Dade County Sec. 14-76(A), Ordinance 26-70

    Test report for more than 5 battery units

    This rule covers a building or space with more than 5 battery-powered exit signs or emergency lights. A licensed electrician or other qualified service provider inspects them. At each fire inspection, give the fire official the test report. It must show that the provider tested all units and that they work.

    Source: Ordinance 26-70

    Code of Miami-Dade County Sec. 14-76(B), Ordinance 26-70

    Test report for generator-powered units

    Where a generator powers the exit signs or the emergency lighting, a licensed electrician or other qualified service provider tests them while the generator runs. The fire official gets the report.

    Source: Ordinance 26-70

    Code of Miami-Dade County Sec. 8CC-10, Ordinance 26-70

    Civil penalty

    The penalty is $250 for a first offense. It is $500 for a second offense within five years. It is $1,000 for a third or later offense within five years.

    Source: Ordinance 26-70

    Ordinance 26-70

    When the county adopted it

    The Board of County Commissioners adopted Ordinance 26-70 on September 1, 2026. Ask Miami-Dade Fire Rescue or your city fire department how they collect the report.

    Source: Ordinance 26-70

    Miami-Dade building recertification

    Recertification report

    Buildings get recertified at 30 years, then every 10 years. Some coastal condo and co-op buildings start at 25 years. The electrical report rates emergency lighting, egress lighting, exit lights and the emergency generator.

    Sources: Recertification page; Electrical recertification form

    Florida, outside the three counties

    State Fire Marshal list

    Local amendments

    Your city or county can add local rules to the Florida Fire Prevention Code. The State Fire Marshal posts the local amendments that it receives.

    Source: State Fire Marshal local amendments

    Your 12-month test log

    Print this log or copy it into a spreadsheet. Write the date, pass or fail, and your initials in each box. Keep the log for the fire official.

    Rows

    Your replacement plan

    What to fix now, what to plan next, and a planning cost range for the material. Every cost on this page is a planning estimate, not a quote.

      See the 36 listed products behind the price ranges

      How we estimate the units

        Send the brief to a lighting designer

        
                  

        What happens next

        1. Copy the brief. This page sends nothing.
        2. Paste the brief into an email or a request form for a lighting designer.
        3. The designer checks the unit count on site and plans the tests and the repairs.
        4. Ask your building department if the repair work needs a permit.

        The brief has your inputs, the rules, the plan and the source links.

        Questions from boards and managers

        How often must we test the emergency lights and exit signs?

        Test each emergency light every month for at least 30 seconds. Keep 3 to 5 weeks between tests. Once a year, test battery-powered emergency lighting for at least 90 minutes. The equipment must stay fully on for each whole test. This is NFPA 101, Section 7.9.3.1.1.

        An exit sign with a battery gets the same tests (Section 7.10.9.2). Sources: Iowa test log, which quotes Section 7.9.3, and the Minnesota Department of Health guide.

        Which edition of the Life Safety Code applies in Florida?

        Florida enforces NFPA 101, Florida 2021 Edition, in the Florida Fire Prevention Code, 8th Edition. The 8th Edition took effect on December 31, 2023. The State Fire Marshal lists the 9th Edition, with NFPA 101, Florida 2024 Edition, for December 31, 2026.

        The Florida amendments in both editions do not change Section 7.9 or Section 7.10. Sources: Rule 69A-60.004, F.A.C. and the State Fire Marshal FFPC page.

        Do self-testing units remove the monthly test?

        A self-testing unit runs a 30-second test and a check by itself at least every 30 days. It shows a failure on a status light. Someone must still look at each unit every month. The 90-minute test is still due once a year (Section 7.9.3.1.2).

        A computer-based system can run the monthly test and the 90-minute test by itself and keep the history (Section 7.9.3.1.3). Source: Minnesota Department of Health guide.

        What records must we keep, and who sees them?

        The owner keeps written records of the visual checks and the tests. The fire official can ask to see them (Section 7.9.3.1.1(5)). For each test, write the unit, the date, the test length, pass or fail, the tester and notes. Our 12-month log has room for these.

        Source: Iowa Department of Inspections, Appeals, and Licensing test log.

        How long must the lights stay on in a power failure?

        At least 90 minutes. At the start, the exit path needs an average of 1 footcandle and at least 0.1 footcandle at any point. After 90 minutes, the level can drop to 0.6 and 0.06 footcandle. The highest level must not be more than 40 times the lowest.

        Source: Florida Building Code, Building, 8th Edition, Sections 1008.3.4 and 1008.3.5.

        How long do the batteries last?

        A Minnesota Department of Health guide says a maintenance-free lead-acid battery might last 5 to 10 years. It says a maintenance-free nickel-cadmium battery might last 10 to 15 years. The maker of your units is the best source. The 90-minute test finds the weak batteries.

        Source: Maintenance of Battery-Operated Emergency Lights.

        What does the new Miami-Dade rule ask for?

        Ordinance 26-70 adds Section 14-76 to the Code of Miami-Dade County. It covers a building or space with more than 5 battery-powered exit signs or emergency lights. A licensed electrician or other qualified service provider inspects them. At a fire inspection, the fire official gets the test report.

        Units on a generator need a similar report, tested while the generator runs. A first offense has a civil penalty of $250. Source: Ordinance 26-70, adopted September 1, 2026.

        Will a building inspection look at our emergency lights?

        In Miami-Dade, the recertification electrical report rates emergency lighting and exit lights. In Broward, the building safety inspection says exit sign lights and emergency lighting must be in good working condition. That inspection comes at 25 years, then every 10 years.

        Fire officials also inspect. Broward's local fire code amendments call for a fire inspection at least once a year. The Palm Beach County schedule lists a yearly fire inspection for apartment buildings. Sources: Miami-Dade electrical recertification form, BORA Policy 05-05, Broward amendments and Palm Beach County amendments.

        Do we need a permit to replace a unit?

        Ask your building department before the work starts. The Broward building safety inspection policy says that some repairs, such as a new bulb in an exit sign, may not need a permit. It says that most other work will need a permit.

        Source: BORA Policy 05-05.

        When is a good time for the 90-minute test?

        The rule asks for the test once a year. NOAA gives June 1 to November 30 as the Atlantic hurricane season. A test in the spring finds weak batteries before the season starts.

        Source: NOAA National Hurricane Center.

        Sources

        We opened and read each source below on the date shown. The NFPA reader needs a free account, so we used state agency documents that quote or cite the code text.

        1. Florida Fire Prevention Code (FFPC). Florida Division of State Fire Marshal. https://myfloridacfo.com/division/sfm/bfp/florida-fire-prevention-code. Checked November 14, 2026. Used for: The 8th Edition took effect on December 31, 2023. The 9th Edition is listed with an effective date of December 31, 2026.
        2. Rule 69A-60.004, F.A.C., NFPA 101, the Life Safety Code, Florida 2021 Edition, Adopted. Florida Administrative Code (flrules.org). https://flrules.org/gateway/ruleNo.asp?id=69A-60.004. Checked November 14, 2026. Used for: Florida adopts NFPA 101, Florida 2021 Edition. The rule version in force took effect on December 31, 2023.
        3. Notice of Proposed Rule, Chapter 69A-60 (9th Edition update). Florida Division of State Fire Marshal. https://www.myfloridacfo.com/docs-sf/state-fire-marshal-libraries/sfm-documents/bfp/florida-fire-prevention-code/69a-60-nopr.pdf. Checked November 14, 2026. Used for: NFPA 101, Florida 2024 Edition, with a proposed effective date of December 31, 2026. The update is the triennial update under s. 633.202(1), F.S.
        4. FFPC 8th Edition, NFPA 101 (2021 edition), Florida amendments. Florida Division of State Fire Marshal. https://myfloridacfo.com/docs-sf/state-fire-marshal-libraries/sfm-documents/bfp/florida-fire-prevention-code/florida-fire-prevention-code-8th-edition-nfpa-101-fl-sp.pdf. Checked November 14, 2026. Used for: The Florida amendments do not change Section 7.9 (emergency lighting) or Section 7.10 (exit signs).
        5. FFPC 9th Edition, NFPA 101 (2024 edition), Florida amendments, Eff. 12/31/2026. Florida Division of State Fire Marshal. https://www.myfloridacfo.com/docs-sf/state-fire-marshal-libraries/sfm-documents/bfp/florida-fire-prevention-code/florida-fire-prevention-code-9th-edition-nfpa101-fl-specific-edits-6-15-2026.pdf. Checked November 14, 2026. Used for: The 9th Edition amendments do not change Section 7.9 or Section 7.10 either.
        6. NFPA 101, Life Safety Code, 2021 edition, free access. National Fire Protection Association. https://link.nfpa.org/free-access/publications/101/2021. Checked November 14, 2026. Used for: The official code text. The free reader asks you to sign in to a free NFPA account.
        7. Emergency Lighting Equipment Test Log (quotes Life Safety Code, 2012 Edition, 7.9.3). Iowa Department of Inspections, Appeals, and Licensing. https://dial.iowa.gov/media/7433/download. Checked November 14, 2026. Used for: The monthly 30-second test with 3 to 5 weeks between tests, the yearly 1.5-hour test for battery systems, written records, and the log columns.
        8. Maintenance of Battery-Operated Emergency Lights (July 2016, revised June 2024). Minnesota Department of Health. https://www.health.mn.gov/facilities/regulation/engineering/lscbatopliting.pdf. Checked November 14, 2026. Used for: Section numbers 7.9.3.1.1 to 7.9.3.1.3 and 7.10.9.2 (2012 edition), self-testing units, written records, and battery service life.
        9. 2023 Florida Building Code, Building, 8th Edition, Chapter 10, Sections 1008.3 and 1013. ICC Digital Codes (Florida Building Commission code). https://codes.iccsafe.org/content/FLBC2023P1/chapter-10-means-of-egress. Checked November 14, 2026. Used for: The 90-minute duration, the light level on the exit path, the areas the emergency system lights, and exit sign power.
        10. Miami-Dade County Ordinance 26-70, local amendments to the FFPC, 9th Edition (Code Sec. 14-76 and Sec. 8CC-10). Miami-Dade Fire Rescue Department, filed with the State Fire Marshal. https://www.myfloridacfo.com/docs-sf/state-fire-marshal-libraries/sfm-documents/bfp/local-amendments/miami-dade-2026.pdf. Checked November 14, 2026. Used for: Test reports for more than 5 battery units and for generator-powered units, and the civil penalties. Adopted September 1, 2026.
        11. Recertification. Miami-Dade County. https://www.miamidade.gov/global/economy/building/recertification.page. Checked November 14, 2026. Used for: Recertification at 30 years and every 10 years after that. Some coastal condo and co-op buildings start at 25 years.
        12. Minimum Inspection Procedural Guidelines for Building Electrical Recertification (revised November 18, 2021). Miami-Dade County Regulatory and Economic Resources. https://wwwx.miamidade.gov/permits/library/electrical-recertification.pdf. Checked November 14, 2026. Used for: The report form rates emergency lighting, building egress illumination, exit lights and the emergency generator.
        13. Broward County Board of Rules and Appeals Policy 05-05, Building Safety Inspection Program. Broward BORA (copy posted by the City of Hollywood). https://fl-hollywood2.civicplus.com/DocumentCenter/View/21696/BORA-Policy-05-05. Checked November 14, 2026. Used for: Inspection at 25 years, then every 10 years. Exit sign lights and emergency lighting must be in good working condition. Permit note for small repairs.
        14. Broward County Local Amendments to the Florida Fire Prevention Code. Broward County, filed with the State Fire Marshal. https://myfloridacfo.com/docs-sf/state-fire-marshal-libraries/sfm-documents/bfp/local-amendments/broward-county-2025.pdf. Checked November 14, 2026. Used for: Section F-103.3.1.7: fire inspections at least once a year, common areas included.
        15. Palm Beach County Local Amendments to the Florida Fire Prevention Code, Appendix A (effective December 31, 2023). Palm Beach County Fire Rescue, filed with the State Fire Marshal. https://myfloridacfo.com/docs-sf/state-fire-marshal-libraries/sfm-documents/bfp/local-amendments/palm-beach-county-2024.pdf. Checked November 14, 2026. Used for: Table 1.3.8.1, the schedule of fire inspections, and Section 1.3.1.1, the area where the amendments apply.
        16. Local Amendments. Florida Division of State Fire Marshal. https://myfloridacfo.com/division/sfm/bfp/local-amendments. Checked November 14, 2026. Used for: The list of local amendments filed by counties and cities.
        17. Mounting Height / Max Spacing Guide (Rev 05/20/26). Dual-Lite (Current Lighting, HLI Solutions). https://cdn.currentlighting.com/site/brochure/Mtg-Height-Max-Spacing_Guide.pdf. Checked November 14, 2026. Used for: The default spacing of 30 ft between compact units in the unit estimate.
        18. Tropical Cyclone Climatology. NOAA National Hurricane Center. https://www.nhc.noaa.gov/climo/. Checked November 14, 2026. Used for: The Atlantic hurricane season runs from June 1 to November 30.
        19. Emergency Lights. 1000Bulbs.com. https://www.1000bulbs.com/category/emergency-lights/. Checked November 14, 2026. Used for: Listed prices of 12 emergency lights (material price basis).
        20. Exit Signs. 1000Bulbs.com. https://www.1000bulbs.com/category/exit-signs/. Checked November 14, 2026. Used for: Listed prices of 12 LED exit signs with a 90-minute battery (material price basis).
        21. Exit Sign Emergency Light Combo. 1000Bulbs.com. https://www.1000bulbs.com/category/exit-sign-emergency-light-combos/. Checked November 14, 2026. Used for: Listed prices of 12 exit sign and emergency light combo units (material price basis).

        Ask a lighting designer about this project

        Send your plan to Holzer Lighting in Boca Raton, Florida. Holzer Lighting designs, specifies and buys lighting for owners, managers, designers and builders.

        A designer reads your brief and contacts you. The designer checks the rules, the light levels and the prices for your site. This page gives planning estimates only.

        You can also email info@holzerlighting.com or call 561.508.8990.

        About Holzer Lighting

        Other free lighting tools:

        Holzer Lighting gets your details and the project brief from this page. They use them only to answer you.